Oil-immersed transformer series with 630, 1,000 or 1,250 kVA rated capacity options.
Technical specifications
| Rated capacity options | 630 kVA, 1,000 kVA, 1,250 kVA |
|---|---|
| Insulation medium | Oil |
Reference Parameters
These figures are reference parameters for custom solution discussions. Final capacity, voltage ratio, frequency, losses, impedance, vector group and tap range are confirmed against your requirements in the approved quotation and technical documents.
Scroll sideways to view all parameters.
Reference data set 0150–2,500 kVA
| Rated capacity (kVA) | No-load loss P₀ (W) | Load loss Pₖ at 75°C (W) | No-load current I₀ (%) | Short-circuit impedance uₖ (%) | Vector group | HV taps |
|---|---|---|---|---|---|---|
| 50 | 37 | 870 | 0.30 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 100 | 55 | 1,500 | 0.30 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 160 | 72 | 2,100 | 0.25 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 200 | 90 | 2,600 | 0.25 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 250 | 110 | 3,100 | 0.25 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 315 | 130 | 3,650 | 0.20 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 400 | 160 | 4,300 | 0.20 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 500 | 190 | 5,150 | 0.20 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 630 | 230 | 6,200 | 0.20 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 800 | 280 | 7,500 | 0.15 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,000 | 340 | 10,300 | 0.15 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,250 | 400 | 12,300 | 0.15 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,600 | 480 | 14,700 | 0.10 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 2,000 | 590 | 17,800 | 0.10 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 2,500 | 710 | 21,200 | 0.10 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
Reference data set 0250–2,500 kVA
| Rated capacity (kVA) | No-load loss P₀ (W) | Load loss Pₖ at 75°C (W) | No-load current I₀ (%) | Short-circuit impedance uₖ (%) | Vector group | HV taps |
|---|---|---|---|---|---|---|
| 50 | 100 | 870 | 0.70 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 100 | 150 | 1,500 | 0.60 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 160 | 210 | 2,100 | 0.60 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 200 | 260 | 2,600 | 0.50 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 250 | 310 | 3,100 | 0.50 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 315 | 360 | 3,650 | 0.50 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 400 | 430 | 4,300 | 0.45 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 500 | 510 | 5,150 | 0.45 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 630 | 610 | 6,200 | 0.40 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 800 | 750 | 7,500 | 0.40 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,000 | 890 | 10,300 | 0.35 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,250 | 1,040 | 12,300 | 0.30 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,600 | 1,250 | 14,700 | 0.30 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 2,000 | 1,550 | 17,800 | 0.30 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 2,500 | 1,830 | 21,200 | 0.25 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
Reference data set 0350–2,500 kVA
| Rated capacity (kVA) | No-load loss P₀ (W) | Load loss Pₖ at 75°C (W) | No-load current I₀ (%) | Short-circuit impedance uₖ (%) | Vector group | HV taps |
|---|---|---|---|---|---|---|
| 50 | 135 | 870 | 1.00 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 100 | 200 | 1,500 | 0.90 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 160 | 270 | 2,100 | 0.80 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 200 | 340 | 2,600 | 0.80 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 250 | 400 | 3,100 | 0.70 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 315 | 480 | 3,650 | 0.70 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 400 | 570 | 4,300 | 0.60 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 500 | 680 | 5,150 | 0.60 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 630 | 810 | 6,200 | 0.50 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 800 | 980 | 7,500 | 0.50 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,000 | 1,150 | 10,300 | 0.50 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,250 | 1,360 | 12,300 | 0.40 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,600 | 1,640 | 14,700 | 0.40 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 2,000 | 2,000 | 17,800 | 0.40 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 2,500 | 2,350 | 21,200 | 0.35 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |