Oil-immersed distribution transformers with 200, 300 or 500 kVA rated capacity options.
Technical specifications
| Rated capacity options | 200 kVA, 300 kVA, 500 kVA |
|---|---|
| Insulation medium | Oil |
The gallery includes a reference cutaway. Confirm the exact internal design and electrical data for the quoted unit.
Reference Parameters
These figures are reference parameters for custom solution discussions. Final capacity, voltage ratio, frequency, losses, impedance, vector group and tap range are confirmed against your requirements in the approved quotation and technical documents.
Scroll sideways to view all parameters.
Reference data set 0150–2,500 kVA
| Rated capacity (kVA) | No-load loss P₀ (W) | Load loss Pₖ at 75°C (W) | No-load current I₀ (%) | Short-circuit impedance uₖ (%) | Vector group | HV taps |
|---|---|---|---|---|---|---|
| 50 | 37 | 870 | 0.30 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 100 | 55 | 1,500 | 0.30 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 160 | 72 | 2,100 | 0.25 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 200 | 90 | 2,600 | 0.25 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 250 | 110 | 3,100 | 0.25 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 315 | 130 | 3,650 | 0.20 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 400 | 160 | 4,300 | 0.20 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 500 | 190 | 5,150 | 0.20 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 630 | 230 | 6,200 | 0.20 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 800 | 280 | 7,500 | 0.15 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,000 | 340 | 10,300 | 0.15 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,250 | 400 | 12,300 | 0.15 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,600 | 480 | 14,700 | 0.10 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 2,000 | 590 | 17,800 | 0.10 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 2,500 | 710 | 21,200 | 0.10 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
Reference data set 0250–2,500 kVA
| Rated capacity (kVA) | No-load loss P₀ (W) | Load loss Pₖ at 75°C (W) | No-load current I₀ (%) | Short-circuit impedance uₖ (%) | Vector group | HV taps |
|---|---|---|---|---|---|---|
| 50 | 100 | 870 | 0.70 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 100 | 150 | 1,500 | 0.60 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 160 | 210 | 2,100 | 0.60 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 200 | 260 | 2,600 | 0.50 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 250 | 310 | 3,100 | 0.50 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 315 | 360 | 3,650 | 0.50 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 400 | 430 | 4,300 | 0.45 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 500 | 510 | 5,150 | 0.45 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 630 | 610 | 6,200 | 0.40 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 800 | 750 | 7,500 | 0.40 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,000 | 890 | 10,300 | 0.35 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,250 | 1,040 | 12,300 | 0.30 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,600 | 1,250 | 14,700 | 0.30 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 2,000 | 1,550 | 17,800 | 0.30 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 2,500 | 1,830 | 21,200 | 0.25 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
Reference data set 0350–2,500 kVA
| Rated capacity (kVA) | No-load loss P₀ (W) | Load loss Pₖ at 75°C (W) | No-load current I₀ (%) | Short-circuit impedance uₖ (%) | Vector group | HV taps |
|---|---|---|---|---|---|---|
| 50 | 135 | 870 | 1.00 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 100 | 200 | 1,500 | 0.90 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 160 | 270 | 2,100 | 0.80 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 200 | 340 | 2,600 | 0.80 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 250 | 400 | 3,100 | 0.70 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 315 | 480 | 3,650 | 0.70 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 400 | 570 | 4,300 | 0.60 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 500 | 680 | 5,150 | 0.60 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 630 | 810 | 6,200 | 0.50 | 4.00 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 800 | 980 | 7,500 | 0.50 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,000 | 1,150 | 10,300 | 0.50 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,250 | 1,360 | 12,300 | 0.40 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 1,600 | 1,640 | 14,700 | 0.40 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 2,000 | 2,000 | 17,800 | 0.40 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |
| 2,500 | 2,350 | 21,200 | 0.35 | 4.50 | Dyn11 / Yyn0 | ±2×2.5% (HV) |