Skip to content

SCB Series Enclosed Dry-Type Transformers

Cast-resin dry-type transformers fitted with a protective enclosure. Include dimensions, ventilation conditions and required enclosure protection in your enquiry.

Request a quote

Cast-resin dry-type transformers fitted with a protective enclosure. Include dimensions, ventilation conditions and required enclosure protection in your enquiry.

Technical specifications

Model series SCB12 / SCB14 / SCB18
Configuration Protective enclosure

The enclosure is a configuration option. Specify the required degree of protection in your enquiry.

Engineering reference specifications

Historical reference: GB/T 10228-2008, §1 and Table 1 (PDF pp. 5–6). 6 kV and 10 kV class, three-phase indoor distribution transformers with off-circuit tapping. The values below are selection references. Confirm the applicable standard and guaranteed values on the selected model’s approved datasheet.

Rated capacity in this reference table 30–2,500 kVA
Primary voltage options 6, 6.3, 6.6, 10, 10.5 or 11 kV
Secondary voltage 400 V
Rated frequency 50 Hz
Primary tap range ±5% or ±2 × 2.5%
Vector group options Dyn11 or Yyn0
Short-circuit impedance 4%, 6% or 8%, depending on the capacity and configuration
Thermal insulation classes in the reference B, F and H

The reference covers the transformer. Confirm the assembly's enclosure IP rating, overall dimensions, ventilation and continuous rating on the approved drawing.