Overview
The ZGS and ZFS series combined transformers are developed and manufactured by our R&D personnel, building upon the advantages of similar products both domestically and internationally, while taking into account the actual power supply conditions in China. The combined transformer is a new type of power distribution equipment in which the transformer core, high-voltage load switch, fuses, and high- and low-voltage connections are housed within a fully sealed oil tank, with transformer oil serving as the insulating medium for live parts, both between phases and to ground.
The combined transformer is suitable for urban public power distribution, high-rise buildings, residential communities, parks, expressways, as well as oil fields, industrial and mining enterprises, and construction sites. It is an essential piece of equipment for urban power grid construction and renovation.
This product complies with the requirements of national standards such as JB/T 10217-2013 Combined Transformers and GB/T 7251.12-2013 Low-voltage switchgear and controlgear assemblies – Part 2: Power switchgear and controlgear assemblies.
Model Designation and Meaning
ZG S13 – Z – 630 / 10
-
Voltage rating (kV)
-
Rated capacity (kVA)
-
High-voltage wiring scheme (“Terminal” type Z, “Ring network” type H)
-
Loss level designation
-
Type (“Integrated” tank type ZG, “Split” tank type ZF)
Service Conditions
-
Altitude: Not exceeding 1000 m
-
Ambient temperature: -25°C to +40°C
-
Relative humidity: Not greater than 95% (daily average)
-
Ground inclination: Not exceeding 3°
-
Wind speed: Not exceeding 35 m/s
-
Suitable for indoor and outdoor locations free from severe impact or vibration, significant pollution and chemically corrosive media, conductive dust, and explosion hazards.
Project configuration
| Assembly configuration | Compact enclosure with a transformer, HV switchgear and LV distribution |
|---|---|
| Electrical ratings to confirm | Transformer kVA, HV/LV ratio, frequency and vector group |
| Switchgear to confirm | Incoming arrangement, rated current and short-circuit rating |
| Installation details to confirm | Enclosure rating, ventilation, footprint and cable entry |
The catalogue overview and detailed table list different capacity ranges. Confirm the selected European-style assembly and transformer rating on a model-specific schedule before using either range.
Technical Specifications
| No. | Item | Unit | High Voltage Side | Transformer | Low Voltage Side |
|---|---|---|---|---|---|
| 1 | Rated Voltage | kV | 10 | – | 0.4 |
| 2 | Max Operating Voltage | kV | 12 | – | – |
| 3 | Rated Frequency | Hz | – | 50 | – |
| 4 | Rated Capacity | kVA | – | 50~1600 | – |
| 5 | Rated Current | A | 10~630 | – | 50~3200 |
| 6 | 1 min Power Frequency Withstand Voltage | kV | – | 35 | 2.5 |
| 7 | Lightning Impulse Withstand Voltage | kV | – | Full wave: 75; Chopped wave: 85 | – |
| 8 | Insulation Oil Breakdown Voltage Value | kV | – | ≥ 35 | – |
| 9 | Winding Temperature Rise Limit | K | – | ≤ 65 | – |
| 10 | Cooling Method | – | – | Oil-immersed Self-cooling (ONAN) | – |
| 11 | Protection Grade | – | IP33 | IP65 | IP33 |
| 12 | Sound Power Level | dB (A) | – | ≤ 45 | – |