Dry-type transformer series with an amorphous alloy core. Provide the intended application and electrical ratings for equipment selection.
Technical specifications
| Model series | SCBH15 / SCBH17 |
|---|---|
| Core material | Amorphous alloy |
The image shows a reference configuration. Confirm the required model, rated capacity and voltage ratio with the sales team.
Engineering reference specifications
Historical reference: GB/T 22072-2008, §1 and Tables 1–2 (PDF pp. 4–6). 6 kV and 10 kV class, three-phase self-cooled dry-type amorphous-core distribution transformers with off-circuit tapping. The values below are selection references. Confirm the applicable standard and guaranteed values on the selected model’s approved datasheet.
| Rated capacity in this reference table | 30–2,500 kVA |
|---|---|
| Primary voltage options | 6, 6.3, 6.6, 10, 10.5 or 11 kV |
| Secondary voltage | 400 V |
| Rated frequency | 50 Hz |
| Primary tap range | ±5% or ±2 × 2.5% |
| Vector group shown | Dyn11 |
| Short-circuit impedance | 4%, 6% or 8%, depending on the capacity and configuration |
| Capacity (kVA) | No-load loss (W) | Load loss, Class F at 120 °C (W) | No-load current (%) | Impedance (%) | Sound power limit [dB(A)] |
|---|---|---|---|---|---|
| 200 | 200 | 2,530 | 1.0 | 4.0 | 67 |
| 250 | 230 | 2,760 | 1.0 | 4.0 | 67 |
| 500 | 360 | 4,880 | 0.8 | 4.0 | 70 |
| 630 | 420 | 5,880 | 0.7 | 4.0 | 71 |
| 630 | 410 | 5,960 | 0.7 | 6.0 | 71 |
| 1,000 | 550 | 8,130 | 0.6 | 6.0 | 72 |
| 1,250 | 650 | 9,690 | 0.6 | 6.0 | 74 |
Load-loss entries use the Class F reference temperature. The two 630 kVA rows are distinct impedance configurations.
Confirm the selected SCBH15 or SCBH17 model, rated capacity and loss figures on its technical sheet.