An amorphous alloy dry-type transformer configuration. Request the outline drawing and technical data for the unit to be quoted.
Technical specifications
| Model series | SCBH15 |
|---|---|
| Core material | Amorphous alloy |
The reference image is labelled SCBH15. Confirm the rated capacity and voltage ratio with the sales team.
Engineering reference specifications
Historical reference: GB/T 22072-2008, §1 and Tables 1–2 (PDF pp. 4–6). 6 kV and 10 kV class, three-phase self-cooled dry-type amorphous-core distribution transformers with off-circuit tapping. The values below are selection references. Confirm the applicable standard and guaranteed values on the selected model’s approved datasheet.
| Rated capacity in this reference table | 30–2,500 kVA |
|---|---|
| Primary voltage options | 6, 6.3, 6.6, 10, 10.5 or 11 kV |
| Secondary voltage | 400 V |
| Rated frequency | 50 Hz |
| Primary tap range | ±5% or ±2 × 2.5% |
| Vector group shown | Dyn11 |
| Short-circuit impedance | 4%, 6% or 8%, depending on the capacity and configuration |
| Capacity (kVA) | No-load loss (W) | Load loss, Class F at 120 °C (W) | No-load current (%) | Impedance (%) | Sound power limit [dB(A)] |
|---|---|---|---|---|---|
| 200 | 200 | 2,530 | 1.0 | 4.0 | 67 |
| 250 | 230 | 2,760 | 1.0 | 4.0 | 67 |
| 500 | 360 | 4,880 | 0.8 | 4.0 | 70 |
| 630 | 420 | 5,880 | 0.7 | 4.0 | 71 |
| 630 | 410 | 5,960 | 0.7 | 6.0 | 71 |
| 1,000 | 550 | 8,130 | 0.6 | 6.0 | 72 |
| 1,250 | 650 | 9,690 | 0.6 | 6.0 | 74 |
Load-loss entries use the Class F reference temperature. The two 630 kVA rows are distinct impedance configurations.
The table provides examples for this core type. Confirm the specific SCBH15 unit's voltage ratio, loss figures and impedance on its technical sheet.