Skip to content

American Style Substations

Pad-mounted, dead-front package substations built to the American arrangement — transformer, HV switching and protection in one tamper-resistant enclosure at ground level, safe for installation in public and residential areas.

Request a quote

Overview

Dead-front construction means no exposed live parts when the compartment is opened, which is what allows this arrangement to be installed on a pad in a car park, a residential street or a commercial forecourt.

Transformer, HV load-break switching, fuse protection and LV distribution are integrated into a single tamper-resistant enclosure.

Key Features

  • Pad-mounted, dead-front design for public-area installation
  • Integrated transformer, HV switching, protection and LV distribution
  • Tamper-resistant, lockable enclosure
  • Compact ground-level footprint, no separate substation building
  • Weatherproof finish for outdoor service

Typical Applications

Residential developments, commercial premises, car parks, campuses and light industrial sites.

Project configuration

Assembly configuration Pad-mounted transformer, HV switching and protection, and LV distribution
Electrical ratings to confirm Transformer kVA, HV/LV ratio, frequency and vector group
Switching and protection to confirm Terminal or ring-feed layout, available fault current, switching and fusing
Installation details to confirm Enclosure rating, dimensions and cable entry

Use the existing catalogue figures as a configuration reference. Confirm ratings and protection for the complete pad-mounted assembly on the approved project schedule.

Technical Specifications

Technical Specifications

No. Item Unit High Voltage Side Transformer Low Voltage Side
1 Rated Voltage kV 10 – 0.4
2 Max. Operating Voltage kV 12 – –
3 Rated Frequency Hz – 50 –
4 Rated Capacity kVA – 50~1600 –
5 Rated Current A 10~630 – 50~3200
6 1 min Power Frequency Withstand Voltage kV – 35 2.5
7 Lightning Impulse Withstand Voltage kV – Full Wave: 75, Chopped Wave: 85 –
8 Insulation Oil Breakdown Voltage Value kV – ≥ 35 –
9 Winding Temperature Rise Limit K – ≤ 65 –
10 Cooling Method – – Oil-immersed Self-cooling –
11 Protection Grade – IP33 IP65 IP33
12 Sound Power Level dB (A) – ≤ 45 –
Contact Close
100%

Loading image…