Oil-Immersed Transformers – 630, 1,000 & 1,250 kVA

Oil-immersed transformer series with 630, 1,000 or 1,250 kVA rated capacity options.

Request a quote

Oil-immersed transformer series with 630, 1,000 or 1,250 kVA rated capacity options.

Technical specifications

Rated capacity options 630 kVA, 1,000 kVA, 1,250 kVA
Insulation medium Oil

Reference Parameters

These figures are reference parameters for custom solution discussions. Final capacity, voltage ratio, frequency, losses, impedance, vector group and tap range are confirmed against your requirements in the approved quotation and technical documents.

Scroll sideways to view all parameters.

Reference data set 0150–2,500 kVA
Rated capacity (kVA) No-load loss P₀ (W) Load loss Pₖ at 75°C (W) No-load current I₀ (%) Short-circuit impedance uₖ (%) Vector group HV taps
50 37 870 0.30 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
100 55 1,500 0.30 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
160 72 2,100 0.25 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
200 90 2,600 0.25 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
250 110 3,100 0.25 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
315 130 3,650 0.20 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
400 160 4,300 0.20 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
500 190 5,150 0.20 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
630 230 6,200 0.20 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
800 280 7,500 0.15 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
1,000 340 10,300 0.15 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
1,250 400 12,300 0.15 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
1,600 480 14,700 0.10 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
2,000 590 17,800 0.10 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
2,500 710 21,200 0.10 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
Reference data set 0250–2,500 kVA
Rated capacity (kVA) No-load loss P₀ (W) Load loss Pₖ at 75°C (W) No-load current I₀ (%) Short-circuit impedance uₖ (%) Vector group HV taps
50 100 870 0.70 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
100 150 1,500 0.60 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
160 210 2,100 0.60 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
200 260 2,600 0.50 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
250 310 3,100 0.50 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
315 360 3,650 0.50 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
400 430 4,300 0.45 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
500 510 5,150 0.45 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
630 610 6,200 0.40 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
800 750 7,500 0.40 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
1,000 890 10,300 0.35 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
1,250 1,040 12,300 0.30 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
1,600 1,250 14,700 0.30 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
2,000 1,550 17,800 0.30 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
2,500 1,830 21,200 0.25 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
Reference data set 0350–2,500 kVA
Rated capacity (kVA) No-load loss P₀ (W) Load loss Pₖ at 75°C (W) No-load current I₀ (%) Short-circuit impedance uₖ (%) Vector group HV taps
50 135 870 1.00 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
100 200 1,500 0.90 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
160 270 2,100 0.80 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
200 340 2,600 0.80 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
250 400 3,100 0.70 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
315 480 3,650 0.70 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
400 570 4,300 0.60 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
500 680 5,150 0.60 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
630 810 6,200 0.50 4.00 Dyn11 / Yyn0 ±2×2.5% (HV)
800 980 7,500 0.50 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
1,000 1,150 10,300 0.50 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
1,250 1,360 12,300 0.40 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
1,600 1,640 14,700 0.40 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
2,000 2,000 17,800 0.40 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)
2,500 2,350 21,200 0.35 4.50 Dyn11 / Yyn0 ±2×2.5% (HV)