SCBH15 Amorphous-Alloy Dry-Type Transformers

An amorphous alloy dry-type transformer configuration. Request the outline drawing and technical data for the unit to be quoted.

Request a quote

An amorphous alloy dry-type transformer configuration. Request the outline drawing and technical data for the unit to be quoted.

Technical specifications

Model series SCBH15
Core material Amorphous alloy

The reference image is labelled SCBH15. Confirm the rated capacity and voltage ratio with the sales team.

Engineering reference specifications

Historical reference: GB/T 22072-2008, §1 and Tables 1–2 (PDF pp. 4–6). 6 kV and 10 kV class, three-phase self-cooled dry-type amorphous-core distribution transformers with off-circuit tapping. The values below are selection references. Confirm the applicable standard and guaranteed values on the selected model’s approved datasheet.

Rated capacity in this reference table 30–2,500 kVA
Primary voltage options 6, 6.3, 6.6, 10, 10.5 or 11 kV
Secondary voltage 400 V
Rated frequency 50 Hz
Primary tap range ±5% or ±2 × 2.5%
Vector group shown Dyn11
Short-circuit impedance 4%, 6% or 8%, depending on the capacity and configuration
Capacity (kVA) No-load loss (W) Load loss, Class F at 120 °C (W) No-load current (%) Impedance (%) Sound power limit [dB(A)]
200 200 2,530 1.0 4.0 67
250 230 2,760 1.0 4.0 67
500 360 4,880 0.8 4.0 70
630 420 5,880 0.7 4.0 71
630 410 5,960 0.7 6.0 71
1,000 550 8,130 0.6 6.0 72
1,250 650 9,690 0.6 6.0 74

Load-loss entries use the Class F reference temperature. The two 630 kVA rows are distinct impedance configurations.

The table provides examples for this core type. Confirm the specific SCBH15 unit's voltage ratio, loss figures and impedance on its technical sheet.