Skip to content

SCBH Series Amorphous-Alloy Dry-Type Transformers

Dry-type transformer series with an amorphous alloy core. Provide the intended application and electrical ratings for equipment selection.

Request a quote

Dry-type transformer series with an amorphous alloy core. Provide the intended application and electrical ratings for equipment selection.

Technical specifications

Model series SCBH15 / SCBH17
Core material Amorphous alloy

The image shows a reference configuration. Confirm the required model, rated capacity and voltage ratio with the sales team.

Engineering reference specifications

Historical reference: GB/T 22072-2008, §1 and Tables 1–2 (PDF pp. 4–6). 6 kV and 10 kV class, three-phase self-cooled dry-type amorphous-core distribution transformers with off-circuit tapping. The values below are selection references. Confirm the applicable standard and guaranteed values on the selected model’s approved datasheet.

Rated capacity in this reference table 30–2,500 kVA
Primary voltage options 6, 6.3, 6.6, 10, 10.5 or 11 kV
Secondary voltage 400 V
Rated frequency 50 Hz
Primary tap range ±5% or ±2 × 2.5%
Vector group shown Dyn11
Short-circuit impedance 4%, 6% or 8%, depending on the capacity and configuration
Capacity (kVA) No-load loss (W) Load loss, Class F at 120 °C (W) No-load current (%) Impedance (%) Sound power limit [dB(A)]
200 200 2,530 1.0 4.0 67
250 230 2,760 1.0 4.0 67
500 360 4,880 0.8 4.0 70
630 420 5,880 0.7 4.0 71
630 410 5,960 0.7 6.0 71
1,000 550 8,130 0.6 6.0 72
1,250 650 9,690 0.6 6.0 74

Load-loss entries use the Class F reference temperature. The two 630 kVA rows are distinct impedance configurations.

Confirm the selected SCBH15 or SCBH17 model, rated capacity and loss figures on its technical sheet.

Contact Close