SCB Series Cast-Resin Dry-Type Transformers

Cast-resin dry-type transformers for indoor power distribution. Share your required rating, voltage ratio and installation conditions for selection and quotation.

Request a quote

Cast-resin dry-type transformers for indoor power distribution. Share your required rating, voltage ratio and installation conditions for selection and quotation.

Technical specifications

Model series SCB12 / SCB14 / SCB18
Insulation Cast resin

The gallery shows different configurations. Confirm the model and rating when requesting a quote.

Engineering reference specifications

Historical reference: GB/T 10228-2008, §1 and Table 1 (PDF pp. 5–6). 6 kV and 10 kV class, three-phase indoor distribution transformers with off-circuit tapping. The values below are selection references. Confirm the applicable standard and guaranteed values on the selected model’s approved datasheet.

Rated capacity in this reference table 30–2,500 kVA
Primary voltage options 6, 6.3, 6.6, 10, 10.5 or 11 kV
Secondary voltage 400 V
Rated frequency 50 Hz
Primary tap range ±5% or ±2 × 2.5%
Vector group options Dyn11 or Yyn0
Short-circuit impedance 4%, 6% or 8%, depending on the capacity and configuration
Thermal insulation classes in the reference B, F and H

The reference table does not distinguish SCB12, SCB14 and SCB18. Use the selected model's technical sheet for the final loss figures, thermal class and dimensions.